ELC-33
Line voltage drop
ΔV ≈ I (R cosφ + X sinφ) per phase. Approximate phasor drop.
Reading speed
PowerIEC 60364
Governing equation
where
- I
- Current (A)
- R
- Resistance (Ω)
- X
- Reactance (Ω)
- \varphi
- Load angle (°)
- \Delta V
- Voltage drop (V)
Lecture brief
Historical brief
Ohm (1827), Kirchhoff (1845) and Maxwell’s circuit reduction still run every board: RLC transients, transformers, skin effect and three-phase power. The sheets are those network laws, not a SPICE deck. This sheet (ELC-33 — Line voltage drop) is the form associated with IEC 60364. Working symbols: , , , . The in-phase component of the IZ drop is I R cosφ + I X sinφ for a lagging load.
Purpose
Purpose: compute from , , , in Electrical via ΔV ≈ I (R cosφ + X sinφ) per phase. Approximate phasor drop. Use it when a real electrical question must be answered in SI before a code check.
Live realistic example
In symbols
Live case. Given , , , , the governing relation yields . A feeder, an I arrow, a voltage sag. Move a slider: the numbers are this situation, not a canned story.
Calculator
Inputs
Outputs
- Voltage drop \Delta V12.11 V
Reading speed
Watch on YouTube
Free library
Full libraryFree PDF / open book
- University Physics Vol. 2 (thermo, E&M)OpenStax · CC BY · Free PDF / open book
- LibreTexts Engineering bookshelfLibreTexts · CC · Free PDF / open book
- SI Brochure (BIPM)BIPM · Free PDF / open book
- NIST fundamental constantsNIST · Free PDF / open book
YouTube channels
00:0 / 00:08
Narration of this film
A feeder, an I arrow, a voltage sag.
The in-phase component of the IZ drop is I R cosφ + I X sinφ for a lagging load.
Reading speed
Watch on YouTube